MODBUS RTU to IEC62056-21 Protocol Meter Gateway With RS232 DB9 Male on Modem Side and RS485 2 Wire Connection on Meter Side
LKM141
MODBUS RTU to IEC62056-21 Protocol Meter Gateway With RS232 DB9 Male on Modem Side and RS485 2 Wire Connection on Meter Side
per one
199.50 USD 210 USD
If you buy less than 5 items you will lose your 5% discount
-    Auto reads Electricity meters that communicates in IEC62056-21 standard and maps in predefined MODBUS register table
-    Configurable Modbus address via Modbus Commands
-    Configurable Reading Period on IEC6056-21 side via Modbus Commands
-    Configurable Reading Table Number on IEC6056-21 side via Modbus Commands
-    Wide range power input: 5V – 24V DC
-    Wide operating temperature range from -40 to 85 °C
-    Very Small form factor, only 2.1 x 4.2 x 4.4cm
-    Customization of reading process and register tables based on client request
-    Firmware upgradable over serial line

MODBUS RTU AND IEC62056-21 CHARACTERISTICS
Modbus RTU Address
Default value is 0x01
Changeable via Modbus Command
Reading Period on IEC62056-21 Protocol Meter Side
Default value is 10 (in seconds)
Changeable via Modbus Command
IEC62056-21 Protocol Meter Read Out Table
Default value is 0x30 = ‘0’in ASCII
Changeable via Modbus Command
IEC62056-21 Protocol Meter Reading Method
Reads each line of table and register data during reading
IEC62056-21 Protocol Meter Read Out Data
Date
Time
Import and Export Active Energy
Import and Export Reactive Energy
Reactive Energy in 4 Quadrants
Import and Export Maximum Demands
Active Power
Phase Currents for each phase
Phase Voltages for each phase
Frequency
Error Code
Extendable/Changeable via firmware change
Monitoring Parameters
IEC Read counter
Time counter (in seconds)
FW version
Queryable via Modbus Commands



INTERFACE AND INDICATORS
RS232 Connector
DB9 Male RS232 Connector. Only Tx-Rx-GND for data transmission
2 – Rx
3 – Tx 
5 – GND
RS485 Connector
Terminal Connector for 2 wire RS485 connection and GND. 
Operation Mode Selection Switch
Selects the operating mode of the device.
( can be different depending on customer specific firmware)



Mode Selection
Modem Side Communication Parameters
Meter Side Communication Parameters
Mode 1 (LED 1 ON)19200 8N1
Starts with 300 baud rate and changes during transmission to target baud rate based on IEC62056-21 protocol
Mode 2 (LED 2 ON)
9600 8N1
Starts with 300 baud rate and changes during transmission to target baud rate based on IEC62056-21 protocol
Mode 3 (LED 3 ON)
19200 8N1
19200 7E1 Fixed
Mode 4 (LED 4 ON)
9600 8N1
9600 7E1 Fixed
LED Indicators
Following LEDs available to show system status.
1 – Mode 1 LED
2 – Mode 2 LED
3 – Mode 3 LED
4 – Mode 4 LED
5 – System LED: Blinks every second
6 – Tx LED: Sending data from Modem Side to Meter Side
7 – Rx LED: Receiving data from Meter Side to Modem Side


FIRMWARE UPGRADE
Upgrade over Serial Line
Available from Modem side Serial Line
RS232 on LKM141


Device must be on operating mode 19200 8N1 for firmware upgrade process.




POWER
Power Switch

Turns  External Power On and OFF
Power Input
5V – 24V DC
Reverse Polarity Protection
Available
Thermal Shutdown Protection
Available




PHYSICAL AND ENVIRONMENTAL CHARACTERISTICS
Enclosure
ABS, IP40
Dimensions
21 x 42 x 44 (h x w x d) mm
Weight
~60gr
Storage Temperature
-55 to 125 °C
Operating Temperature
-40 to 85 °C 
Operating Humidity
5% to 95%Non-condensing



LKM141: Modem side RS232, Meter side RS485, Modbus RTU to IEC 62056-21 Protocol Meter gateway
BSB Series Industrial Unmanaged Ethernet Switch
BSB Series Industrial Unmanaged Ethernet Switch
TLM Series LoRa and LoRaWAN Modems
TLM Series LoRa and LoRaWAN Modems
LKM Series Electricity Meter Protocol to Modbus Protocol Gateways
LKM Series Electricity Meter Protocol to Modbus Protocol Gateways
CKL Series Modbus, Serial to Ethernet Gateway
CKL Series Modbus, Serial to Ethernet Gateway
STG Series WMBus (Wireless MBus) - Modbus TCP/RTU Gateway
STG Series WMBus (Wireless MBus) - Modbus TCP/RTU Gateway
HUR Series Modbus TCP and RTU Remote I/O Devices
HUR Series Modbus TCP and RTU Remote I/O Devices
MBC Series IEC62056-21 Protocol Auto Baud Changer
MBC Series IEC62056-21 Protocol Auto Baud Changer
KMK Series Optical Probes for Energy Meters